Loading...
HomeMy WebLinkAbout08.a (Handout) re Seismic Improvements Program$.a. �andoaf) Item 8.a SEISMIC IMPROVEMENTS PROGRAM Presentation to Board of Directors September 2, 2010 Seismic Study has Identified Deficiencies in Critical District Facilities Concord Fault Proximity to District Facilities Preliminary Seismic Status • Work completed (HHWCF, Standby Power Facility, and new CSOD Building) • Pre - design ■ Headquarters Office Building (HOB) ■ Pump & Blower Building (PBB) ■ Defer • Plant Operations Building (except critical works) • Solids Conditioning Building (pending regulations) ■ 4737 Warehouse (work with Real Estate Committee) Headquarters Office Building (HOB) ■ Deficiency ■ Does not meet Life Safety: 2007 CBC, ASCE 41, FEMA 351 • Flexible building structure • Steel moment frames with wood diaphragm ■ Impact ■ Over 100 employees present ■ Disruption to customer service activity Pump & Blower Building (PBB) ■ Deficiency ■ Does not meet Life Safety: 2007 CBC, ASCE 41, FEMA 351 • Excessive displacements • Steel moment frames ■ Columns over- stressed ■ Impact ■ Treatment Process: Aeration Air SteamTurbines, Electric Blower, Primary Effluent and Final Effluent Pumps, and Service Air Compressors. Recommendation ■ Recommended by the Capital Projects Committee ■ Approve the authorizations to perform seismic pre- design for ■ Headquarters Office Building (DP 8226) ■ Pump & Blower Building (DP 7291) ■ Will return to Board with findings and determine next steps